AXEN X-FORCE Commercial

Model code: KS-350W/N7BP
✓ BUS eligibleAir Source (ASHP)CommercialHeating & cooling
Heating capacity
35 kW
SCOP
4.59
W35
COP
4.3
A7/W35
Max flow temp
85°C
Sound power
70 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

✓ BUS eligible

Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).

PEL certificate: MR 50726487 0001/001

Grant also needs an MCS-certified installer and a qualifying system design.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity35 kW
Max heating output (low temp)35 kW at A7/W55
COP (heating)4.3 at A7/W35
SCOP (heating)4.59 at W35
Operating range (air)-25 to 35 °C
Heating flow temperature25–85 °C
Cooling performance
Cooling capacity35 kW
Max cooling output (high temp)35 kW at A35/W7
EER (cooling)2.88 at A35/W7
SEER (cooling)6.88 at W7
Cooling flow temperature7–18 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level70 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1821 × 1350 × 520 mm
Operational Weight310 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.