← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Carrier 30XW-V

Model code: 30XWHV 1710
Water Source (WSHP)CommercialHeating & cooling
Carrier 30XW-V
Heating capacity
2067 kW
SCOP
5.87
W35
COP
4.16
W10/W45
Max flow temp
50°C
Sound power
106 dB(A)
Refrigerant
R134a

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR134a
ModeHeating & cooling
Heating performance
Heating capacity2067 kW
Max heating output (low temp)1932 kW at W10/W45
COP (heating)4.16 at W10/W45
SCOP (heating)5.87 at W35
Heating flow temperature3.3–50 °C
Cooling performance
Cooling capacity2040 kW
Max cooling output (high temp)1741 kW at W35/W7
EER (cooling)4.94 at W35/W7
SEER (cooling)7.34 at W7
Electrical, acoustic and physical
Power input464.42 kW
Electrical supply380-415V (Three Phase)
Sound power level106 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2051 × 1255 × 4730 mm
Operational Weight7808 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.