Carrier 61CW-Z742
Specifications and technical data
Water Source (WSHP)CommercialR1234ze736 kW
| Manufacturer | Carrier |
|---|---|
| Model | 61CW-Z742 |
| Model code | None |
| Heat pump type | Water Source (WSHP) |
| Application | Commercial |
| Refrigerant | R1234ze |
| Mode | Heating only |
| Heating capacity | 736 kW |
| COP | 2.8 at W10/W75 |
| Operating range (air) | 11 to 29 °C |
| Flow temperature | 57–90 °C |
| Power input | 255 kW |
| Dimensions (H×W×D) | 1951 × 2088 × 4630 mm |
| Weight | 4800 kg |
| Data added | 2026-06-24 |
| Data source | Manufacturer Data Sheet |
Notes
Very high temperature water-source heat pump for industrial and district heating applications.
W29/W90 data used. W10/W75 alternative capacity 524 kW, COP 2.8. Evaporator operating range +11/+29°C; condenser outlet range +57/+90°C. R1234ze charge 200 kg. Reference dimensions/weight; final values depend on operating point.
✓ Manually verified by Heat Pump Database
✎ Suggest a correction to this data
Data is compiled from manufacturer sources and may contain errors or gaps. Always confirm specifications with the manufacturer before making decisions.
More from Carrier
30XWHPZE 301
WSHP · 322 kW · SCOP 6.2
30XWHPZE 401
WSHP · 448 kW · SCOP 6.74
30XWHPZE 451
WSHP · 509 kW · SCOP 6.81
30XWHPZE 551
WSHP · 657 kW · SCOP 6.48
30XWHPZE 601
WSHP · 698 kW · SCOP 6.53
30XWHPZE 651
WSHP · 758 kW · SCOP 6.57
30XWHPZE 801
WSHP · 916 kW · SCOP 6.79
30XWHPZE 901
WSHP · 1012 kW · SCOP 6.97
Other Water Source (WSHP) heat pumps
DYNACIAT LG 080
WSHP · 30 kW · SCOP 5.35
DYNACIAT LG 090
WSHP · 35 kW · SCOP 5.33
DYNACIAT LG 100
WSHP · 38 kW · SCOP 5.24
DYNACIAT LG 120
WSHP · 44 kW · SCOP 5.28
DYNACIAT LG 130
WSHP · 51 kW · SCOP 5.23
DYNACIAT LG 150
WSHP · 56 kW · SCOP 5.26