← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Carrier AquaSnap 30FQ

Model code: 30FQ 045 HALSRVP4U
Air Source (ASHP)CommercialHeating & cooling
Carrier AquaSnap 30FQ
Heating capacity
45.1 kW
SCOP
3.61
Not stated
COP
3.32
A7/W45
Max flow temp
60°C
Sound power
77 dB(A)
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity45.1 kW
Max heating output (low temp)45.1 kW at A7/W45
COP (heating)3.32 at A7/W45
SCOP (heating)3.61 at Not stated
Operating range (air)from -20 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity38.3 kW
Max cooling output (high temp)38.3 kW at A35/W7
EER (cooling)2.76 at A35/W7
Electrical, acoustic and physical
Power input13.6 kW
Electrical supply380-415V (Three Phase)
Sound power level77 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1670 × 2460 × 1265 mm
Operational Weight680 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.