Product data sheetheatpumpdatabase.com

Carrier AquaSnap 30RQ
Model code: 30RQ 040-A
Air Source (ASHP)CommercialHeating & cooling

Heating capacity
38.6 kW
SCOP
3.25
W35
COP
3.52
A7/W35
Max flow temp
50°C
Sound power
80 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 38.6 kW |
| Max heating output (low temp) | 40.7 kW at A7/W45 |
| COP (heating) | 3.52 at A7/W35 |
| SCOP (heating) | 3.25 at W35 |
| Operating range (air) | -10 to 40 °C |
| Heating flow temperature | 20–50 °C |
| Cooling performance | |
| Cooling capacity | 54.2 kW |
| Max cooling output (high temp) | 39.2 kW at A35/W7 |
| EER (cooling) | 2.85 at A35/W7 |
| SEER (cooling) | 3.32 at W7 |
| Electrical, acoustic and physical | |
| Power input | 17.5 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 80 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1790 × 824 × 1002 mm |
| Operational Weight | 305 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.