Carrier AquaSnap 61AQ

Model code: 61AQ 140P
Air Source (ASHP)CommercialHeating & cooling
Carrier AquaSnap 61AQ
Heating capacity
125 kW
SCOP
4.16
W35
COP
3.97
A7/W35
Max flow temp
75°C
Sound power
83.5 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity125 kW
Max heating output (low temp)125 kW at A7/W55
COP (heating)3.97 at A7/W35
SCOP (heating)4.16 at W35
Operating range (air)-25 to 50 °C
Heating flow temperature20–75 °C
Cooling performance
Cooling capacity120 kW
Max cooling output (high temp)120 kW at A35/W7
EER (cooling)2.23 at A35/W7
SEER (cooling)4.4 at W7
Electrical, acoustic and physical
Power input31.49 kW
Electrical supply380-415V (Three Phase)
Sound power level83.5 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2045 × 2267 × 1815 mm
Operational Weight1138 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.