Product data sheetheatpumpdatabase.com

Carrier AquaSnap 61WG
Model code: 61WG 080
Water Source (WSHP)CommercialHeating only

Heating capacity
101 kW
SCOP
6.11
W35
COP
5.28
W10/W35
Max flow temp
65°C
Sound power
73 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Water Source (WSHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 101 kW |
| Max heating output (low temp) | 93 kW at W7/W55 |
| COP (heating) | 5.28 at W10/W35 |
| SCOP (heating) | 6.11 at W35 |
| Operating range (air) | from -12 °C |
| Heating flow temperature | up to 65 °C |
| Cooling performance | |
| Cooling capacity | 113 kW |
| Max cooling output (high temp) | 84 kW at W35/W7 |
| EER (cooling) | 4.65 at A35/W7 |
| SEER (cooling) | 5.72 at W7 |
| Electrical, acoustic and physical | |
| Power input | 18.94 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 73 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 901 × 880 × 1474 mm |
| Operational Weight | 413 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.