Product data sheetheatpumpdatabase.com

CIAT DYNACIAT LG
Model code: DYNACIAT LG 090
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
35 kW
SCOP
5.33
W35
COP
5.48
W10/W35
Max flow temp
55°C
Sound power
69 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Water Source (WSHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 35 kW |
| Max heating output (low temp) | 35 kW at W7/W35 |
| COP (heating) | 5.48 at W10/W35 |
| SCOP (heating) | 5.33 at W35 |
| Operating range (air) | -12 to 20 °C |
| Heating flow temperature | 30–55 °C |
| Cooling performance | |
| Cooling capacity | 39 kW |
| Max cooling output (high temp) | 39 kW at W35/W7 |
| EER (cooling) | 4.68 at W35/W7 |
| SEER (cooling) | 4.78 at Not stated |
| Electrical, acoustic and physical | |
| Power input | 10.8 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 69 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 901 × 1044 × 600 mm |
| Operational Weight | 200 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.