CIAT DYNACIAT LG

Model code: DYNACIAT LG 180
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
70 kW
SCOP
5.95
W35
COP
5.49
W10/W35
Max flow temp
55°C
Sound power
72 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating & cooling
Heating performance
Heating capacity70 kW
Max heating output (low temp)70 kW at W7/W35
COP (heating)5.49 at W10/W35
SCOP (heating)5.95 at W35
Operating range (air)-12 to 20 °C
Heating flow temperature30–55 °C
Cooling performance
Cooling capacity78 kW
Max cooling output (high temp)78 kW at W35/W7
EER (cooling)4.65 at W35/W7
SEER (cooling)5.41 at Not stated
Electrical, acoustic and physical
Power input21.5 kW
Electrical supply380-415V (Three Phase)
Sound power level72 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)901 × 1474 × 880 mm
Operational Weight386 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.