Product data sheetheatpumpdatabase.com

Clade Maple 500/650 kW SN
Air Source (ASHP)CommercialHeating only
Heating capacity
650 kW
SCOP
2.6
W55
COP
2.55
A7/W55
Max flow temp
70°C
Sound power
97 dB(A)
Refrigerant
R744
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R744 |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 650 kW |
| Max heating output (low temp) | 400 kW at A-5/W55 |
| COP (heating) | 2.55 at A7/W55 |
| SCOP (heating) | 2.6 at W55 |
| Operating range (air) | -15 to 40 °C |
| Heating flow temperature | 55–70 °C |
| Electrical, acoustic and physical | |
| Power input | 225.9 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 97 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2382 × 7508 × 2400 mm |
| Operational Weight | 6477 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.