← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clade Rowan 2

Air Source (ASHP)CommercialHeating & cooling
Heating capacity
128 kW
SCOP
3.7
COP
3.6
A7/W45
Max flow temp
80°C
Sound power
87 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity128 kW
Max heating output (low temp)94 kW at A-5/W55
COP (heating)3.6 at A7/W45
SCOP (heating)3.7 (conditions not stated)
Operating range (air)-15 to 40 °C
Heating flow temperature25–80 °C
Cooling performance
Cooling capacity134 kW
Max cooling output (high temp)104 kW at A35/W7
EER (cooling)2 at A35/W7
Electrical, acoustic and physical
Power input128 kW
Electrical supply380-415V (Three Phase)
Sound power level87 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2636 × 2400 × 1700 mm
Operational Weight2200 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.