Product data sheetheatpumpdatabase.com

Clade Rowan 2
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
128 kW
SCOP
3.7
COP
3.6
A7/W45
Max flow temp
80°C
Sound power
87 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 128 kW |
| Max heating output (low temp) | 94 kW at A-5/W55 |
| COP (heating) | 3.6 at A7/W45 |
| SCOP (heating) | 3.7 (conditions not stated) |
| Operating range (air) | -15 to 40 °C |
| Heating flow temperature | 25–80 °C |
| Cooling performance | |
| Cooling capacity | 134 kW |
| Max cooling output (high temp) | 104 kW at A35/W7 |
| EER (cooling) | 2 at A35/W7 |
| Electrical, acoustic and physical | |
| Power input | 128 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 87 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2636 × 2400 × 1700 mm |
| Operational Weight | 2200 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.