← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clade Rowan 600/400 LN

Air Source (ASHP)CommercialHeating only
Heating capacity
454.5 kW
SCOP
3.7
W35
COP
3.9
A7/W35
Max flow temp
65°C
Sound power
78 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating only
Heating performance
Heating capacity454.5 kW
Max heating output (low temp)426.5 kW at A-5/W55
COP (heating)3.9 at A7/W35
SCOP (heating)3.7 at W35
Operating range (air)-15 to 40 °C
Heating flow temperature35–65 °C
Electrical, acoustic and physical
Power input178.6 kW
Electrical supply380-415V (Three Phase)
Sound power level78 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2840 × 7515 × 2400 mm
Operational Weight10105 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.