← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet Elfoenergy Magnum HW

Model code: WSAN-XEM HW 40.4
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
123 kW
SCOP
3.95
W35
COP
3.52
A7/W45
Max flow temp
65°C
Sound power
86 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating & cooling
Heating performance
Heating capacity123 kW
Max heating output (low temp)123 kW at A7/W45
COP (heating)3.52 at A7/W45
SCOP (heating)3.95 at W35
Operating range (air)from -20 °C
Heating flow temperatureup to 65 °C
Cooling performance
Cooling capacity98.6 kW
Max cooling output (high temp)98.6 kW at A35/W7
EER (cooling)2.8 at A35/W7
SEER (cooling)3.35 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level86 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1800 × 3400 × 1812 mm
Operational Weight1418 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.