← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet Large Evo

Model code: WiSAN-YEE1 50.4
Air Source (ASHP)CommercialHeating & cooling
Clivet Large Evo
Heating capacity
130 kW
SCOP
4.12
W35
COP
3.01
A7/W45
Max flow temp
60°C
Sound power
85 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity130 kW
Max heating output (low temp)130 kW at A7/W45
COP (heating)3.01 at A7/W45
SCOP (heating)4.12 at W35
Operating range (air)from -20 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity127 kW
Max cooling output (high temp)127 kW at A35/W7
EER (cooling)2.49 at A35/W7
SEER (cooling)4.51 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level85 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1900 × 3310 × 1200 mm
Operational Weight966 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.