← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet Large Evo

Model code: WiSAN-YEE1 70.4
Air Source (ASHP)CommercialHeating & cooling
Clivet Large Evo
Heating capacity
210 kW
SCOP
4.15
W35
COP
3.1
A7/W45
Max flow temp
60°C
Sound power
88 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity210 kW
Max heating output (low temp)210 kW at A7/W45
COP (heating)3.1 at A7/W45
SCOP (heating)4.15 at W35
Operating range (air)from -20 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity176 kW
Max cooling output (high temp)176 kW at A35/W7
EER (cooling)2.34 at A35/W7
SEER (cooling)4.45 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level88 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1900 × 4300 × 1200 mm
Operational Weight1250 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.