← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet LARGE EVO PL 70.4

Model code: WiSAN-YEE1 PL 70.4
Air Source (ASHP)CommercialHeating & cooling
Clivet LARGE EVO PL 70.4
Heating capacity
232 kW
SCOP
4.12
W35
COP
3.18
A7/W45
Max flow temp
60°C
Sound power
89 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity232 kW
Max heating output (low temp)232 kW at A7/W45
COP (heating)3.18 at A7/W45
SCOP (heating)4.12 at W35
Operating range (air)-20 to 48 °C
Heating flow temperatureup to 60 °C
Cooling performance
Cooling capacity181 kW
Max cooling output (high temp)181 kW at A35/W7
EER (cooling)2.85 at A35/W7
SEER (cooling)4.64 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level89 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1937 × 4349 × 1530 mm
Operational Weight2020 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.