← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet Spinchiller4 Excellence

Model code: WSAN-YSC4 225.6
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
640 kW
COP
3.22
A7/W45
Max flow temp
55°C
Sound power
93 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity640 kW
Max heating output (low temp)640 kW at A7/W45
COP (heating)3.22 at A7/W45
Operating range (air)from -15 °C
Heating flow temperatureup to 55 °C
Cooling performance
Cooling capacity610 kW
Max cooling output (high temp)610 kW at A35/W7
EER (cooling)3.08 at A35/W7
SEER (cooling)4.89 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level93 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2520 × 7045 × 2250 mm
Operational Weight4761 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.