← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Clivet Spinchiller4 Premium

Model code: WSAN-YSC4 110.4
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
285 kW
SCOP
3.83
W35
COP
3.09
A7/W45
Max flow temp
55°C
Sound power
88 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity285 kW
Max heating output (low temp)285 kW at A7/W45
COP (heating)3.09 at A7/W45
SCOP (heating)3.83 at W35
Operating range (air)from -15 °C
Heating flow temperatureup to 55 °C
Cooling performance
Cooling capacity275 kW
Max cooling output (high temp)275 kW at A35/W7
EER (cooling)2.7 at A35/W7
SEER (cooling)4.35 at W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level88 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2520 × 3118 × 2250 mm
Operational Weight2434 kg