Product data sheetheatpumpdatabase.com

Clivet Thunder
Model code: WiSAN-P 18.1
✓ MCS listedAir Source (ASHP)CommercialHeating & cooling

Heating capacity
55.1 kW
SCOP
4.36
W35
COP
3.19
A7/W45
Max flow temp
75°C
Sound power
77 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.
MCS certification
✓ MCS listed
Certificate: ICIM-PDC-000336 / 00
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 55.1 kW |
| Max heating output (low temp) | 55.1 kW at A7/W45 |
| COP (heating) | 3.19 at A7/W45 |
| SCOP (heating) | 4.36 at W35 |
| Operating range (air) | from -20 °C |
| Heating flow temperature | up to 75 °C |
| Cooling performance | |
| Cooling capacity | 49.9 kW |
| Max cooling output (high temp) | 49.9 kW at A35/W7 |
| EER (cooling) | 2.58 at A35/W7 |
| SEER (cooling) | 4.73 at W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 77 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2240 × 2384 × 1094 mm |
| Operational Weight | 757 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.