Product data sheetheatpumpdatabase.com

Clivet Thunder
Model code: WiSAN-P 25.2
✓ MCS listedAir Source (ASHP)CommercialHeating & cooling

Heating capacity
78.6 kW
SCOP
4.7
W35
COP
3.14
A7/W45
Max flow temp
75°C
Sound power
78 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.
MCS certification
✓ MCS listed
Certificate: ICIM-PDC-000337 / 00
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 78.6 kW |
| Max heating output (low temp) | 78.6 kW at A7/W45 |
| COP (heating) | 3.14 at A7/W45 |
| SCOP (heating) | 4.7 at W35 |
| Operating range (air) | from -20 °C |
| Heating flow temperature | up to 75 °C |
| Cooling performance | |
| Cooling capacity | 67.8 kW |
| Max cooling output (high temp) | 67.8 kW at A35/W7 |
| EER (cooling) | 2.86 at A35/W7 |
| SEER (cooling) | 5.47 at W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 78 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2240 × 3402 × 1094 mm |
| Operational Weight | 1021 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.