← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

CTC EcoAir C100 C116 (230V)

Model code: 591005001
✓ BUS eligible✓ MCS listedAir Source (ASHP)CommercialHeating & cooling
Heating capacity
17.97 kW
SCOP
5.15
W35
COP
5
A7/W35
Max flow temp
75°C
Sound power
52 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

✓ BUS eligible

Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).

PEL certificate: 047-A1010

Grant also needs an MCS-certified installer and a qualifying system design.

MCS certification

✓ MCS listed

Certificate: 047-A1010

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity17.97 kW
Max heating output (low temp)11.4 kW at A-7/W35
COP (heating)5 at A7/W35
SCOP (heating)5.15 at W35
Operating range (air)-25 to 38 °C
Heating flow temperature25–75 °C
Cooling performance
Cooling capacity17.53 kW
Max cooling output (high temp)13.79 kW at A35/W7
EER (cooling)3.73 at A35/W7
Electrical, acoustic and physical
Electrical supply220-240V (Single Phase)
Sound power level52 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1397 × 1204 × 488 mm
Operational Weight142 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.