← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Daikin EWWD-J-SS

Model code: EWWD250J-SS
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
308.4 kW
SCOP
4.46
Not stated
COP
5.17
W35/W7
Max flow temp
35°C
Sound power
89 dB(A)
Refrigerant
R134a

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeWater Source (WSHP)
ApplicationCommercial
RefrigerantR134a
ModeHeating & cooling
Heating performance
Heating capacity308.4 kW
COP (heating)5.17 at W35/W7
SCOP (heating)4.46 at Not stated
Heating flow temperature30–35 °C
Cooling performance
Cooling capacity255.3 kW
EER (cooling)4.26 at A35/W7
SEER (cooling)5.09 at W7
Cooling flow temperaturefrom -10 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level89 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1020 × 913 × 2684 mm
Operational Weight1600 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.