Daikin EWYK-CZ

Model code: EWYK050CZPA2
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
49.25 kW
SCOP
4.62
W35
COP
3.76
A7/W45
Max flow temp
75°C
Sound power
87 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity49.25 kW
COP (heating)3.76 at A7/W45
SCOP (heating)4.62 at W35
Operating range (air)-20 to 46 °C
Heating flow temperature20–75 °C
Cooling performance
Cooling capacity44.29 kW
EER (cooling)3.47 at A35/W7
SEER (cooling)5.54 at W7
Cooling flow temperature-15–20 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level87 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1878 × 3016 × 816 mm

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.