Product data sheetheatpumpdatabase.com

Daikin EWYT-B
Model code: EWYT235B-SS
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
236 kW
SCOP
3.34
Not stated
COP
2.87
Not stated
Max flow temp
60°C
Sound power
91 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 236 kW |
| COP (heating) | 2.87 at Not stated |
| SCOP (heating) | 3.34 at Not stated |
| Operating range (air) | -20 to 46 °C |
| Heating flow temperature | 20–60 °C |
| Cooling performance | |
| Cooling capacity | 212 kW |
| EER (cooling) | 2.69 at Not stated |
| SEER (cooling) | 3.96 at Not stated |
| Cooling flow temperature | -13–20 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 91 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1800 × 1195 × 3225 mm |
| Operational Weight | 1825 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.