Product data sheetheatpumpdatabase.com

Dimplex LI
Model code: LI 1826C
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
21.3 kW
SCOP
4.09
W35
COP
4.8
A7/W35
Max flow temp
60°C
Sound power
60 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 21.3 kW |
| Max heating output (low temp) | 18.3 kW at A-7/W35 |
| COP (heating) | 4.8 at A7/W35 |
| SCOP (heating) | 4.09 at W35 |
| Operating range (air) | -22 to 35 °C |
| Heating flow temperature | 22–60 °C |
| Cooling performance | |
| Cooling capacity | 19.2 kW |
| Max cooling output (high temp) | 14.9 kW at A35/W7 |
| EER (cooling) | 3.3 at A27/W18 |
| Cooling flow temperature | 9–20 °C |
| Electrical, acoustic and physical | |
| Power input | 9.9 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 60 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1770 × 750 × 1000 mm |
| Operational Weight | 326 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.