Product data sheetheatpumpdatabase.com

Dimplex System S
Model code: LIA 0608BWCF M
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
7.35 kW
COP
5
A7/W35
Max flow temp
65°C
Sound power
58 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 7.35 kW |
| Max heating output (low temp) | 6.21 kW at A-7/W35 |
| COP (heating) | 5 at A7/W35 |
| Operating range (air) | -25 to 35 °C |
| Heating flow temperature | 12–65 °C |
| Cooling performance | |
| Cooling capacity | 8.52 kW |
| Max cooling output (high temp) | 7.22 kW at A35/W10 |
| EER (cooling) | 3.55 at A35/W10 |
| Cooling flow temperature | 7–25 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 220-240V (Single Phase) |
| Sound power level | 58 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 712 × 1008 × 426 mm |
| Operational Weight | 60 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.