Product data sheetheatpumpdatabase.com

Ecoforest ecoGEO+ B/C
Model code: ecoGEO+ B/C 3-12 (230V)
Ground Source (GSHP)ResidentialHeating & cooling
Heating capacity
2.1–16 kW
SCOP
4.95
W35
COP
4.6
B0/W35
Max flow temp
60°C
Sound power
54 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Ground Source (GSHP) |
| Application | Residential |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 2.1–16 kW |
| Max heating output (low temp) | 13.8 kW at B0/W55 |
| COP (heating) | 4.6 at B0/W35 |
| SCOP (heating) | 4.95 at W35 |
| Operating range (air) | -25 to 35 °C |
| Heating flow temperature | 10–60 °C |
| Cooling performance | |
| Cooling capacity | 2.1–15 kW |
| Max cooling output (high temp) | 15 kW at B30/W7 |
| EER (cooling) | 5.2 at B30/W7 |
| Cooling flow temperature | 7–30 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 220-240V (Single Phase) |
| Sound power level | 54 dB(A) (Sound Power LW(A)) |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.