Product data sheetheatpumpdatabase.com

Ecoforest ecoGEO+ HP
Model code: ecoGEO+ HP 170 R454B
Ground Source (GSHP)ResidentialHeating & cooling
Heating capacity
21.1–80 kW
SCOP
5.21
W35
COP
4.6
B0/W35
Max flow temp
60°C
Sound power
72 dB(A)
Refrigerant
R454B
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Ground Source (GSHP) |
| Application | Residential |
| Refrigerant | R454B |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 21.1–80 kW |
| Max heating output (low temp) | 76.8 kW at B0/W55 |
| COP (heating) | 4.6 at B0/W35 |
| SCOP (heating) | 5.21 at W35 |
| Operating range (air) | -20 to 35 °C |
| Heating flow temperature | 20–60 °C |
| Cooling performance | |
| Cooling capacity | 21.4–73.7 kW |
| Max cooling output (high temp) | 73.7 kW at B30/W7 |
| EER (cooling) | 4.5 at B30/W7 |
| Cooling flow temperature | 7–30 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 72 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1074 × 1009 × 916 mm |
| Operational Weight | 465 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.