Product data sheetheatpumpdatabase.com
ELCO AEROTOP M
Model code: AEROTOP M 048
✓ MCS listedAir Source (ASHP)CommercialHeating & cooling
Heating capacity
62.4 kW
SCOP
3.91
W35
COP
4.01
A7/W35
Max flow temp
54°C
Sound power
84 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.
MCS certification
✓ MCS listed
Certificate: ICIM-PDC-000097-00-01
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 62.4 kW |
| Max heating output (low temp) | 31.1 kW at A-7/W35 |
| COP (heating) | 4.01 at A7/W35 |
| SCOP (heating) | 3.91 at W35 |
| Heating flow temperature | up to 54 °C |
| Cooling performance | |
| Cooling capacity | 57.7 kW |
| Max cooling output (high temp) | 42 kW at A35/W7 |
| EER (cooling) | 2.69 at A35/W7 |
| SEER (cooling) | 4 at W7 |
| Cooling flow temperature | from 5 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 84 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1326 × 2204 × 1042 mm |
| Operational Weight | 530 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.