← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

ELCO AEROTOP M

Model code: AEROTOP M 024
✓ BUS eligible✓ MCS listedAir Source (ASHP)CommercialHeating & cooling
Heating capacity
30.5 kW
SCOP
4.3
W35
COP
4.17
A7/W35
Max flow temp
54°C
Sound power
75 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

✓ BUS eligible

Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).

PEL certificate: ICIM-PDC-000096-00-01

Grant also needs an MCS-certified installer and a qualifying system design.

MCS certification

✓ MCS listed

Certificate: ICIM-PDC-000096-00-01

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity30.5 kW
Max heating output (low temp)16.3 kW at A-7/W35
COP (heating)4.17 at A7/W35
SCOP (heating)4.3 at W35
Heating flow temperatureup to 54 °C
Cooling performance
Cooling capacity31.3 kW
Max cooling output (high temp)22.3 kW at A35/W7
EER (cooling)3.02 at A35/W7
SEER (cooling)4.63 at W7
Cooling flow temperaturefrom 5 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level75 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1180 × 1861 × 991 mm
Operational Weight298 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.