← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Exinda Commercial Air to Water Heat Pump

Model code: FBMBHT4B2E3
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
72.86 kW
COP
3.89
A8/W35
Max flow temp
60°C
Refrigerant
R32

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity72.86 kW
Max heating output (low temp)42.87 kW at A-8/W35
COP (heating)3.89 at A8/W35
Operating range (air)-25 to 43 °C
Heating flow temperature35–60 °C
Cooling performance
Cooling capacity34 kW
Max cooling output (high temp)34 kW at A35/W7
Cooling flow temperature7–27 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Dimensions (H×W×D)2118 × 1135 × 1035 mm
Operational Weight400 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.