Product data sheetheatpumpdatabase.com

Fenagy H-1800 CO₂
Air Source (ASHP)CommercialHeating only
Heating capacity
900–1800 kW
COP
3.25
A5/W70
Max flow temp
85°C
Sound power
102 dB(A)
Refrigerant
R744
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R744 |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 900–1800 kW |
| COP (heating) | 3.25 at A5/W70 |
| Operating range (air) | -20 to 40 °C |
| Heating flow temperature | 40–85 °C |
| Electrical, acoustic and physical | |
| Power input | 570 kW |
| Electrical supply | Not stated |
| Sound power level | 102 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2400 × 11000 × 1400 mm |
| Operational Weight | 12000 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.