Haier Split Aqua

Model code: AU162FYCRA(HW)
✓ BUS eligible✓ MCS listedAir Source (ASHP)ResidentialHeating & cooling
Heating capacity
16 kW
SCOP
4.13
W35
COP
4.02
A7/W35
Max flow temp
60°C
Sound power
68 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

✓ BUS eligible

Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).

PEL certificate: MCS HP0359/04

Grant also needs an MCS-certified installer and a qualifying system design.

MCS certification

✓ MCS listed

Certificate: 24.01.019 AU162FYCRA(HW)

General
Heat pump typeAir Source (ASHP)
ApplicationResidential
RefrigerantR32
ModeHeating & cooling
Heating performance
Heating capacity16 kW
Max heating output (low temp)16 kW at A7/W35
COP (heating)4.02 at A7/W35
SCOP (heating)4.13 at W35
Operating range (air)-25 to 30 °C
Heating flow temperature25–60 °C
Cooling performance
Cooling capacity16 kW
Max cooling output (high temp)14.5 kW at A35/W7
EER (cooling)4.4 at A35/W18
Electrical, acoustic and physical
Electrical supply220-240V (Single Phase)
Sound power level68 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1500 × 950 × 370 mm
Operational Weight157 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.