← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Hamworthy Tyneham

Model code: Tyneham 50kW
Air Source (ASHP)CommercialHeating only
Heating capacity
50.2 kW
SCOP
4.16
W35
COP
4.11
A7/W35
Max flow temp
55°C
Sound power
82 dB(A)
Refrigerant
R32

Boiler Upgrade Scheme

On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR32
ModeHeating only
Heating performance
Heating capacity50.2 kW
Max heating output (low temp)50.2 kW at A7/W35
COP (heating)4.11 at A7/W35
SCOP (heating)4.16 at W35
Operating range (air)-20 to 40 °C
Heating flow temperatureup to 55 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level82 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1920 × 1920 × 1110 mm
Operational Weight535 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.