Product data sheetheatpumpdatabase.com
Hamworthy Tyneham CO2
Model code: Tyneham CO2 95kW
Air Source (ASHP)CommercialHeating only
Heating capacity
95 kW
COP
3.4
A7/W65
Max flow temp
70°C
Sound power
75 dB(A)
Refrigerant
R744
Boiler Upgrade Scheme
On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R744 |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 95 kW |
| Max heating output (low temp) | 95 kW at A7/W35 |
| COP (heating) | 3.4 at A7/W65 |
| Operating range (air) | from -15 °C |
| Heating flow temperature | up to 70 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 75 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1853 × 3051 × 1160 mm |
| Operational Weight | 1260 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.