← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Hamworthy Tyneham CO2

Model code: Tyneham CO2 95kW
Air Source (ASHP)CommercialHeating only
Heating capacity
95 kW
COP
3.4
A7/W65
Max flow temp
70°C
Sound power
75 dB(A)
Refrigerant
R744

Boiler Upgrade Scheme

On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR744
ModeHeating only
Heating performance
Heating capacity95 kW
Max heating output (low temp)95 kW at A7/W35
COP (heating)3.4 at A7/W65
Operating range (air)from -15 °C
Heating flow temperatureup to 70 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level75 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1853 × 3051 × 1160 mm
Operational Weight1260 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.