Product data sheetheatpumpdatabase.com
Hamworthy Tyneham
Model code: Tyneham 14kW 1PH
✓ BUS eligibleAir Source (ASHP)CommercialHeating only
Heating capacity
14.1 kW
SCOP
4.48
W35
COP
4.85
A7/W35
Max flow temp
55°C
Sound power
68 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
✓ BUS eligible
Listed on the Ofgem BUS Product Eligibility List (24 Sep 2026).
Grant also needs an MCS-certified installer and a qualifying system design.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 14.1 kW |
| Max heating output (low temp) | 14.1 kW at A7/W35 |
| COP (heating) | 4.85 at A7/W35 |
| SCOP (heating) | 4.48 at W35 |
| Operating range (air) | -20 to 40 °C |
| Heating flow temperature | up to 55 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 230-240V (Single Phase) |
| Sound power level | 68 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1409 × 1044 × 455 mm |
| Operational Weight | 121 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.