← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Harnitek Heat Pump Power XR

Model code: YHEPK-30V4MB
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
15.2–28.7 kW
COP
4.43
A7/W35
Max flow temp
60°C
Sound power
62 dB(A)
Refrigerant
R410A

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR410A
ModeHeating & cooling
Heating performance
Heating capacity15.2–28.7 kW
Max heating output (low temp)29.4 kW at A7/W45
COP (heating)4.43 at A7/W35
Operating range (air)-25 to 45 °C
Heating flow temperature10–60 °C
Cooling performance
Cooling capacity15.2–26.8 kW
Max cooling output (high temp)21.2 kW at A35/W7
EER (cooling)4.68 at A35/W18
Cooling flow temperaturefrom 5 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level62 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1450 × 1295 × 455 mm
Operational Weight180 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.