Product data sheetheatpumpdatabase.com

Hitachi Yutaki S
Model code: Yutaki S 20kW
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
9–25.5 kW
SCOP
3.88
W35
COP
4.3
A7/W35
Max flow temp
60°C
Sound power
73 dB(A)
Refrigerant
R410A
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R410A |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 9–25.5 kW |
| Max heating output (low temp) | 14.5 kW at A-7/W55 |
| COP (heating) | 4.3 at A7/W35 |
| SCOP (heating) | 3.88 at W35 |
| Operating range (air) | -25 to 43 °C |
| Heating flow temperature | 20–60 °C |
| Cooling performance | |
| Cooling capacity | 16.4 kW |
| EER (cooling) | 3.12 |
| Electrical, acoustic and physical | |
| Power input | 4.65 kW |
| Electrical supply | 220-240V (Single Phase) |
| Sound power level | 73 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1380 × 950 × 370 mm |
| Operational Weight | 137 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.