Product data sheetheatpumpdatabase.com

Hoval Belaria fit
Model code: Belaria fit (40)
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
4.7–40.6 kW
SCOP
4.46
W35
COP
3.6
A2/W35
Max flow temp
60°C
Sound power
75 dB(A)
Refrigerant
R32
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R32 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 4.7–40.6 kW |
| Max heating output (low temp) | 30.7 kW at A-7/W35 |
| COP (heating) | 3.6 at A2/W35 |
| SCOP (heating) | 4.46 at W35 |
| Heating flow temperature | up to 60 °C |
| Cooling performance | |
| Cooling capacity | 59.3 kW |
| Max cooling output (high temp) | 43.9 kW at A35/W7 |
| EER (cooling) | 3.1 at A35/W7 |
| SEER (cooling) | 4.3 at Not stated |
| Electrical, acoustic and physical | |
| Power input | 17 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 75 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1480 × 2300 × 1060 mm |
| Operational Weight | 513 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.