Product data sheetheatpumpdatabase.com

Hoval Belaria pro
Model code: Belaria pro (25)
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
12.6–24 kW
SCOP
5.6
W55
COP
5.5
A7/W35
Max flow temp
70°C
Sound power
61 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 12.6–24 kW |
| Max heating output (low temp) | 22.1 kW at A-7/W35 |
| COP (heating) | 5.5 at A7/W35 |
| SCOP (heating) | 5.6 at W55 |
| Heating flow temperature | up to 70 °C |
| Cooling performance | |
| Cooling capacity | 13–20.9 kW |
| Max cooling output (high temp) | 19.1 kW at A35/W7 |
| EER (cooling) | 3.4 at A35/W7 |
| SEER (cooling) | 3.2 at W7 |
| Electrical, acoustic and physical | |
| Power input | 11.9 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 61 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1464 × 1928 × 997 mm |
| Operational Weight | 460 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.