← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Hoval Belaria pro

Model code: Belaria pro (20)
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
10.6–19.2 kW
SCOP
5.6
W55
COP
5.7
A7/W35
Max flow temp
70°C
Sound power
61 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity10.6–19.2 kW
Max heating output (low temp)17.7 kW at A-7/W35
COP (heating)5.7 at A7/W35
SCOP (heating)5.6 at W55
Heating flow temperature22–70 °C
Cooling performance
Cooling capacity13–20.9 kW
Max cooling output (high temp)19.1 kW at A35/W7
EER (cooling)3.4 at A35/W7
SEER (cooling)3.2 at W7
Electrical, acoustic and physical
Power input7.8 kW
Electrical supply380-415V (Three Phase)
Sound power level61 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)1464 × 1928 × 997 mm

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.