Product data sheetheatpumpdatabase.com

Ideal Heating ECOMOD 290HT
Model code: ECOMOD 290HT 40kW
Air Source (ASHP)CommercialHeating only
Heating capacity
40.1 kW
SCOP
4.09
W35
COP
4.1
A7/W35
Max flow temp
75°C
Sound power
82 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating only |
| Heating performance | |
| Heating capacity | 40.1 kW |
| Max heating output (low temp) | 40.1 kW at A7/W35 |
| COP (heating) | 4.1 at A7/W35 |
| SCOP (heating) | 4.09 at W35 |
| Operating range (air) | -20 to 40 °C |
| Heating flow temperature | up to 75 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 82 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1980 × 1895 × 1110 mm |
| Operational Weight | 535 kg |