Product data sheetheatpumpdatabase.com

Keyter Medea 3210
Model code: KZV 3210 I N S4C
Water Source (WSHP)CommercialHeating & cooling
Heating capacity
237 kW
SCOP
6
W35
COP
5.56
W7/W35
Max flow temp
60°C
Refrigerant
R454B
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Water Source (WSHP) |
| Application | Commercial |
| Refrigerant | R454B |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 237 kW |
| Max heating output (low temp) | 237 kW at W7/W35 |
| COP (heating) | 5.56 at W7/W35 |
| SCOP (heating) | 6 at W35 |
| Heating flow temperature | up to 60 °C |
| Cooling performance | |
| Cooling capacity | 201.3 kW |
| Max cooling output (high temp) | 201.3 kW at W35/W7 |
| EER (cooling) | 4.71 at A35/W7 |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Dimensions (H×W×D) | 1500 × 2550 × 800 mm |
| Operational Weight | 1143 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.