Keyter Qu4tro 2375

Model code: K4A 2375 I N S3C
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
357.8 kW
COP
3.46
A7/W45
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity357.8 kW
Max heating output (low temp)357.8 kW at A7/W45
COP (heating)3.46 at A7/W45
Cooling performance
Cooling capacity284.8 kW
Max cooling output (high temp)284.8 kW at A35/W7
EER (cooling)2.43 at A35/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Dimensions (H×W×D)2280 × 2980 × 2100 mm
Operational Weight2691 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.