← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Keyter Ziran Pro 4200

Model code: KWR 4200 I V S4D
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
252.8 kW
COP
3.86
A7/W35
Max flow temp
70°C
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity252.8 kW
Max heating output (low temp)222 kW at A7/W55
COP (heating)3.86 at A7/W35
Operating range (air)from -25 °C
Heating flow temperature30–70 °C
Cooling performance
Cooling capacity193.9 kW
Max cooling output (high temp)193.9 kW at A35/W7
EER (cooling)2.5 at A35/W7
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Dimensions (H×W×D)2550 × 5350 × 1300 mm

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.