Kronoterm ADAPTMAX
Model code: ADAPTMAX10140
✓ MCS listedAir Source (ASHP)CommercialHeating & cooling

Heating capacity
141.4 kW
SCOP
5.8
W35
COP
5.32
A7/W35
Max flow temp
75°C
Sound power
55 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
On the Ofgem PEL, but rated above the 45 kW BUS capacity limit.
MCS certification
✓ MCS listed
Certificate: 011-1W1031
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 141.4 kW |
| Max heating output (low temp) | 123.1 kW at A-7/W35 |
| COP (heating) | 5.32 at A7/W35 |
| SCOP (heating) | 5.8 at W35 |
| Operating range (air) | -25 to 40 °C |
| Heating flow temperature | 15–75 °C |
| Cooling performance | |
| Cooling capacity | 121 kW |
| Max cooling output (high temp) | 121 kW at A35/W7 |
| EER (cooling) | 2.74 at A35/W7 |
| Cooling flow temperature | 7–25 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 55 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 1683 × 6625 × 960 mm |
| Operational Weight | 2500 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.