Product data sheetheatpumpdatabase.com

MAXA HWA2-AH 0290
Model code: HWA2-AH 0290
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
84.4 kW
SCOP
3.873
W35
COP
4.14
A7/W35
Max flow temp
78°C
Sound power
54 dB(A)
Refrigerant
R290
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R290 |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 84.4 kW |
| Max heating output (low temp) | 84.4 kW at A7/W35 |
| COP (heating) | 4.14 at A7/W35 |
| SCOP (heating) | 3.873 at W35 |
| Heating flow temperature | up to 78 °C |
| Cooling performance | |
| Cooling capacity | 72.8 kW |
| Max cooling output (high temp) | 86.3 kW at A35/W18 |
| EER (cooling) | 3.1 at A35/W7 |
| SEER (cooling) | 4.287 at W7 |
| Cooling flow temperature | 7–18 °C |
| Electrical, acoustic and physical | |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 54 dB(A) (Sound Pressure Lp at 10 m) |
| Dimensions (H×W×D) | 2250 × 2570 × 1135 mm |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.