MAXA HWA2-AH 0290

Model code: HWA2-AH 0290
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
84.4 kW
SCOP
3.873
W35
COP
4.14
A7/W35
Max flow temp
78°C
Sound power
54 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity84.4 kW
Max heating output (low temp)84.4 kW at A7/W35
COP (heating)4.14 at A7/W35
SCOP (heating)3.873 at W35
Heating flow temperatureup to 78 °C
Cooling performance
Cooling capacity72.8 kW
Max cooling output (high temp)86.3 kW at A35/W18
EER (cooling)3.1 at A35/W7
SEER (cooling)4.287 at W7
Cooling flow temperature7–18 °C
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level54 dB(A) (Sound Pressure Lp at 10 m)
Dimensions (H×W×D)2250 × 2570 × 1135 mm

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.