← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Mitsubishi Electric NX-Q-G06

Model code: NX-Q-G06-0604/LN
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
150.2 kW
COP
2.98
A7/W45
Max flow temp
55°C
Sound power
86 dB(A)
Refrigerant
R454B

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR454B
ModeHeating & cooling
Heating performance
Heating capacity150.2 kW
Max heating output (low temp)150.2 kW at A7/W45
COP (heating)2.98 at A7/W45
Operating range (air)-15 to 46 °C
Heating flow temperature20–55 °C
Cooling performance
Cooling capacity137 kW
Max cooling output (high temp)137 kW at A35/W7
EER (cooling)2.47 at A35/W7
SEER (cooling)3.59 at Not stated
Electrical, acoustic and physical
Power input47.5 kW
Electrical supply380-415V (Three Phase)
Sound power level86 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2150 × 3110 × 2220 mm
Operational Weight1660 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.