Product data sheetheatpumpdatabase.com

Mitsubishi Electric NX-Q-G06
Model code: NX-Q-G06-0904/LN
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
212.2 kW
COP
3.02
A7/W45
Max flow temp
55°C
Sound power
87 dB(A)
Refrigerant
R454B
Boiler Upgrade Scheme
Not found on the Ofgem BUS Product Eligibility List.
MCS certification
No MCS listing recorded.
| General | |
|---|---|
| Heat pump type | Air Source (ASHP) |
| Application | Commercial |
| Refrigerant | R454B |
| Mode | Heating & cooling |
| Heating performance | |
| Heating capacity | 212.2 kW |
| Max heating output (low temp) | 212.2 kW at A7/W45 |
| COP (heating) | 3.02 at A7/W45 |
| Operating range (air) | -15 to 46 °C |
| Heating flow temperature | 20–55 °C |
| Cooling performance | |
| Cooling capacity | 190.8 kW |
| Max cooling output (high temp) | 190.8 kW at A35/W7 |
| EER (cooling) | 2.31 at A35/W7 |
| SEER (cooling) | 3.7 at Not stated |
| Electrical, acoustic and physical | |
| Power input | 68.6 kW |
| Electrical supply | 380-415V (Three Phase) |
| Sound power level | 87 dB(A) (Sound Power LW(A)) |
| Dimensions (H×W×D) | 2150 × 4110 × 2220 mm |
| Operational Weight | 2130 kg |
Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.