← Back to product pageFree data sheet, no subscription
heatpumpdatabase
Product data sheetheatpumpdatabase.com

Modutherm AW290

Model code: 50kW
Air Source (ASHP)CommercialHeating & cooling
Heating capacity
50 kW
SCOP
4.69
W35
COP
4.4
A7/W35
Max flow temp
85°C
Sound power
83 dB(A)
Refrigerant
R290

Boiler Upgrade Scheme

Not found on the Ofgem BUS Product Eligibility List.

MCS certification

No MCS listing recorded.

General
Heat pump typeAir Source (ASHP)
ApplicationCommercial
RefrigerantR290
ModeHeating & cooling
Heating performance
Heating capacity50 kW
Max heating output (low temp)50 kW at A7/W55
COP (heating)4.4 at A7/W35
SCOP (heating)4.69 at W35
Operating range (air)-30 to 43 °C
Heating flow temperatureup to 85 °C
Cooling performance
Cooling capacity45 kW
Max cooling output (high temp)42 kW at A35/W7
EER (cooling)4.4 at A35/W18
Electrical, acoustic and physical
Electrical supply380-415V (Three Phase)
Sound power level83 dB(A) (Sound Power LW(A))
Dimensions (H×W×D)2060 × 1049 × 1169 mm
Operational Weight445 kg

Test conditions: A = outdoor air °C, W = flow water °C (e.g. A7/W35 = 7°C air, 35°C flow). Compare COP and SCOP only at the same conditions.